For information, call:  866.347.3353            
          450.437.3473            

Compressed Air Foam - Foam supply




Foam concentrate is provided from a tank that is pressurized by the system air supply only upon system activation.  An internal siphon tube directs the foam concentrate into the system trim.

ICAF Compressed Air Foam Systems do not use bladder tanks, greatly simplifying installation and maintenance !

Click here to view datasheet.

Compressed Air Foam Systems:  AFFF for flammable liquid hazards 

Technical details:

  • FM & MEA Approved.

  • Stainless steel pressure vessel stamped according to ASME Section VIII, Div. 1. 

  • Available from 5 to 550 USGallons, sized according to FireFlex Systems calculations.

  • External level sight-glass tube and foam sampling test port.

  • Pressure relief valve and pressure gauge.

  • NO BLADDER in tank !

  • Approved Foam Concentrates:
      Hydrocarbons:  - National Foam Aer-O-Lite 3%
                             - National Foam Aer-O-Water 3EM 3%
      Polar solvents:  - Ansulite 3X3 LV Alcohol Resistant

  • Design densities used:
      Hydrocarbons:  0.04 GPM/Sq.Ft. at 2% concentration.
      Polar solvents:  0.06 GPM/Sq.Ft. at 6% concentration.

Home - About us - Compressed Air Foam - Viking TotalPac2
Archives - Search - Distributors - Events - News - Feedback - Site Map